Single Burners
RatioMatic
RatioMatic uses a pressure-ratio regulator that compensates for changing conditions without a second gas adjustment.
RatioMatic uses a pressure-ratio regulator that compensates for changing conditions without a second gas adjustment. A directly driven air butterfly avoids external linkage, while rapid nozzle mixing stabilizes the flame. The family spans several capacities, and its maximum turndown is explicitly dependent on burner size and chamber conditions.
Features & Benefits
- Maximum Operating Temperature
- 1900 deg F (1040 deg C)
- Control Motor Specifications
- ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible
- Combustion Air Requirements
- Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C)
- Valve Train Requirement
- Main gas shut‑off valve train per NFPA recommendations
- Excess Air Capability
- 10 to 15% at high fire|Higher at low fire
- Air/Gas Ratio Control
- Ratio regulator with impulse line
- Gas Pipe Connections
- Threaded Gas Connections (customer‑selected type)
- Combustion Principle
- Nozzle-mix, ratio-controlled combustion
- Burner Configuration
- Vertical Down, Vertical Up, Horizontal
- Primary Application
- Direct and indirect air heating; oven applications
- Fuel Pressure Range
- Must meet datasheet specs; low pressure may cause unsafe operation
- Altitude Adjustment
- Capacity reduced ~3% per 1000 ft above sea level
- Flame Supervision
- Flame rod (RM0050 to RM0700), UV scanner (all models)
- Flame Monitoring
- Individual or multiple burner control options
- Hazard Warnings
- Hot surfaces, combustion risks, crystalline silica exposure
- Turndown Ratio
- High‑turndown option available|Wide turndown
- Combustor Tube
- Alloy (low temp), SiC or refractory block (high temp)
- Ignition Type
- Direct Spark Ignition (low fire or bypass start gas)
- Control Motor
- Kromschröder IC 20 actuator or bracket for customer‑supplied motor
- Burner Family
- RatioMatic®
- Burner Design
- Modular design with various configurations
- Loading Line
- Plastic, Braided Stainless Steel, or Rigid Stainless Tube
- Flame Sensor
- Flame rod or UV scanner
- Burner Type
- Nozzle‑mix air‑heating burner
- Fuel Type
- Natural Gas, Propane, Butane
- Approvals
- NFPA Compliant (e.g., dual gas shut-off valves)
- Automatic ratio compensation avoids a separate gas adjustment.
- Direct drive removes a potentially slipping external linkage.
Applications
- Process-air heating
Detailed capabilities
Pressure-ratio compensation and direct drive
RatioMatic's regulator automatically follows changing operating conditions, reducing the need to readjust a second gas setting. A directly driven butterfly controls combustion air without linkage that could slip or bind. Rapid fuel/air mixing retains a stable flame and releases heat into the chamber rather than concentrating it at the oven wall, supporting emission-sensitive air-heating processes.
Capacity and turndown belong to the installation
The published family covers 500,000–30,000,000 Btu/hr. Its stated maximum 90:1 turndown depends on burner size and chamber conditions; it is not a fixed value for every burner or every chamber. The source reports low NOx, CO and aldehydes but does not turn those general performance descriptions into one common emissions limit for all possible installations.
Features and benefits
- Automatic ratio compensation avoids a separate gas adjustment.
- Direct drive removes a potentially slipping external linkage.
Published application context
- Process-air heating
Overview
- Models
- RM0050 - RM3000
- Burner Type
- Nozzle‑mix air‑heating burner
Operating/Process Temperature Ranges
- Maximum Operating Temperature
- 1900 deg F (1040 deg C)
Motor Specifications
- Control Motor Specifications
- ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible
- Control Motor
- Kromschröder IC 20 actuator or bracket for customer‑supplied motor
Air & Combustion Air Specifications
- Combustion Air Requirements
- Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C)
- Excess Air Capability
- 10 to 15% at high fire; Higher at low fire
- Air/Gas Ratio Control
- Ratio regulator with impulse line
Actuation, Valve & Motion Control Specifications
- Valve Train Requirement
- Main gas shut‑off valve train per NFPA recommendations
Connections & Interfaces
- Gas Pipe Connections
- Threaded Gas Connections (customer‑selected type)
Combustion, Mixing & Fuel Dynamics
- Combustion Principle
- Nozzle-mix, ratio-controlled combustion
Combustion, Fuel & Mixing Sub‑Systems
- Burner Configuration
- Vertical Down, Vertical Up, Horizontal
Applications & Compatibility
- Primary Application
- Direct and indirect air heating; oven applications
Pressure Specifications
- Fuel Pressure Range
- Must meet datasheet specs; low pressure may cause unsafe operation
Operating Limits, Durability & Lifecycle
- Altitude Adjustment
- Capacity reduced ~3% per 1000 ft above sea level
Ignition, Flame & Supervision Specifications
- Flame Supervision
- Flame rod (RM0050 to RM0700), UV scanner (all models)
- Flame Monitoring
- Individual or multiple burner control options
- Ignition Type
- Direct Spark Ignition (low fire or bypass start gas)
- Flame Sensor
- Flame rod or UV scanner
Safety, Protection & Reliability
- Hazard Warnings
- Hot surfaces, combustion risks, crystalline silica exposure
Performance, Flow & Capacity
- Turndown Ratio
- High‑turndown option available; Wide turndown
Combustion Design & Characteristics
- Combustor Tube
- Alloy (low temp), SiC or refractory block (high temp)
Product Design & Configuration
- Burner Family
- RatioMatic®
- Burner Design
- Modular design with various configurations
Mechanical Design & Adjustment Characteristics
- Loading Line
- Plastic, Braided Stainless Steel, or Rigid Stainless Tube
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas, Propane, Butane
Standards & Certifications
- Approvals
- NFPA Compliant (e.g., dual gas shut-off valves)
| Parameter | Published value / configuration |
|---|---|
| Models | RM0050 - RM3000 |
| Burner Type | Nozzle‑mix air‑heating burner |
| Maximum Operating Temperature | 1900 deg F (1040 deg C) |
| Control Motor Specifications | ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible |
| Control Motor | Kromschröder IC 20 actuator or bracket for customer‑supplied motor |
| Combustion Air Requirements | Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C) |
| Excess Air Capability | 10 to 15% at high fire; Higher at low fire |
| Air/Gas Ratio Control | Ratio regulator with impulse line |
| Valve Train Requirement | Main gas shut‑off valve train per NFPA recommendations |
| Gas Pipe Connections | Threaded Gas Connections (customer‑selected type) |
| Combustion Principle | Nozzle-mix, ratio-controlled combustion |
| Burner Configuration | Vertical Down, Vertical Up, Horizontal |
| Primary Application | Direct and indirect air heating; oven applications |
| Fuel Pressure Range | Must meet datasheet specs; low pressure may cause unsafe operation |
| Altitude Adjustment | Capacity reduced ~3% per 1000 ft above sea level |
| Flame Supervision | Flame rod (RM0050 to RM0700), UV scanner (all models) |
| Flame Monitoring | Individual or multiple burner control options |
| Ignition Type | Direct Spark Ignition (low fire or bypass start gas) |
| Flame Sensor | Flame rod or UV scanner |
| Hazard Warnings | Hot surfaces, combustion risks, crystalline silica exposure |
| Turndown Ratio | High‑turndown option available; Wide turndown |
| Combustor Tube | Alloy (low temp), SiC or refractory block (high temp) |
| Burner Family | RatioMatic® |
| Burner Design | Modular design with various configurations |
| Loading Line | Plastic, Braided Stainless Steel, or Rigid Stainless Tube |
| Fuel Type | Natural Gas, Propane, Butane |
| Approvals | NFPA Compliant (e.g., dual gas shut-off valves) |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 10020506 | NZL,MACHG,RM,RM0300,NAT | Request quotation |
| 10024135 | NZL,RM,RM0300,PROP/BUTANE | Request quotation |
| 10024136 | NZL,RM,RM0300,NAT | Request quotation |
| 10039113 | NZL,RM,200,NAT,TWO PC ASY | Request quotation |
| 10039114 | NZL,RM,200,PROP/BUT,TWO PC ASY | Request quotation |
| 10039141 | NZL,RM,500,NAT,TWO PC ASY | Request quotation |
| 10039142 | NZL,RM,500,PROP/BUT,TWO PC ASY | Request quotation |
| 10039143 | NZL,RM,700,NAT,TWO PC ASY | Request quotation |
| 10039144 | NZL,RM,700,PROP/BUT,TWO PC ASY | Request quotation |
| 10040035 | NZL,BRNR,RM400,V3,NAT,SS,WLDMNT | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
RatioMatic Product Image · Manufacturer ownership retained; republication licence not independently confirmed
RatioMatic Product Diagram · Manufacturer ownership retained; republication licence not independently confirmed
RatioMatic Flame Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.