Single Burners
RatioAir
RatioAir combines a velocity burner with an integral blower for confined chambers, high excess-air duties and unusual fuels.
RatioAir combines a velocity burner with an integral blower for confined chambers, high excess-air duties and unusual fuels. Rear disassembly and quick-change ignition/sensing rods support service without entering the chamber. Ratio control, interchangeable piping orientation and thread choices adapt the package, with chamber temperature and flame-speed limits stated separately.
Features & Benefits
- Control Motor Specifications
- ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible
- Combustion Air Requirements
- Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C)
- Ignition Transformer Specs
- 6000 to 8000 VAC, ≥ 0.02 A, Full wave output
- Excess Air Capability
- 10 to 15% at high fire|Higher at low fire
- Air/Gas Ratio Control
- Ratio regulator with impulse line
- Outlet Tube Velocity
- Standard, Medium (250 ft/s), High (500 ft/s)
- Combustion Principle
- Nozzle‑mix burner
- Burner Configuration
- Vertical Down, Vertical Up, Horizontal
- Primary Application
- Direct and indirect air heating
- Fuel Pressure Range
- Must meet datasheet specs; low pressure may cause unsafe operation
- Altitude Adjustment
- Capacity reduced ~3% per 1000 ft above sea level
- Blower Motor Types
- NEMA (60Hz), IEC (50Hz), TEFC or automotive duty
- Flame Supervision
- Flame rod (RA0025 to RA0200), UV scanner (all models)
- Safety Standards
- NFPA Compliant (e.g., dual gas shut-off valves)
- Flame Monitoring
- Individual or multiple burner control options
- Shut-Off Valves
- Automatic/manual, NFPA compliant
- Safety Features
- Air pressure switch, flame monitoring, limit switches
- Ratio Regulator
- Maintains air/gas ratio via impulse line
- Pressure Switch
- Detects low air pressure
- Hazard Warnings
- Hot surfaces, combustion risks, crystalline silica exposure
- Combustion Type
- Nozzle-mix, direct or indirect fired
- Turndown Ratio
- Wide turndown (high‑turndown option available)
- Combustor Tube
- Alloy (low temp), SiC or refractory block (high temp)
- Blower Options
- Integrated or remote blower (SMJ series)
- Ignition Type
- Direct Spark Ignition (low fire or bypass start gas)
- Control Motor
- Kromschröder IC 20 actuator or bracket for customer motor
- Burner Family
- RatioAir®
- Burner Design
- Modular design with various configurations
- Loading Line
- Plastic, Braided Stainless Steel, or Rigid Stainless Tube
- Flame Sensor
- Flame rod or UV scanner
- Burner Type
- Nozzle‑mix air‑heating burner
- Fuel Type
- Natural Gas, Propane, Butane
- Rear service access avoids entering the firing chamber.
Applications
- Confined firing chambers
- High-temperature air heating
- Unusual or low-Btu fuel heating
Detailed capabilities
Service access, fuel choice and confined chambers
RatioAir packages its blower with a velocity burner capable of high excess-air or ratio-controlled operation. Rear disassembly avoids entering the chamber, and quick-change spark/flame rods shorten service work. Standard nozzles accept the listed gases and qualified unusual fuels; an optional air filter and left/right piping adapt the package. High chamber-temperature capability is distinct from the flame-speed figure.
Features and benefits
- Rear service access avoids entering the firing chamber.
Published application context
- Confined firing chambers
- High-temperature air heating
- Unusual or low-Btu fuel heating
Motor Specifications
- Control Motor Specifications
- ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible
- Blower Motor Types
- NEMA (60Hz), IEC (50Hz), TEFC or automotive duty
- Control Motor
- Kromschröder IC 20 actuator or bracket for customer motor
Air & Combustion Air Specifications
- Combustion Air Requirements
- Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C)
- Excess Air Capability
- 10 to 15% at high fire; Higher at low fire
- Air/Gas Ratio Control
- Ratio regulator with impulse line
Ignition, Flame & Supervision Specifications
- Ignition Transformer Specs
- 6000 to 8000 VAC, ≥ 0.02 A, Full wave output
- Flame Supervision
- Flame rod (RA0025 to RA0200), UV scanner (all models)
- Flame Monitoring
- Individual or multiple burner control options
- Ignition Type
- Direct Spark Ignition (low fire or bypass start gas)
- Flame Sensor
- Flame rod or UV scanner
Processing & Performance Metrics
- Outlet Tube Velocity
- Standard, Medium (250 ft/s), High (500 ft/s)
Combustion, Mixing & Fuel Dynamics
- Combustion Principle
- Nozzle‑mix burner
Combustion, Fuel & Mixing Sub‑Systems
- Burner Configuration
- Vertical Down, Vertical Up, Horizontal
Applications & Compatibility
- Primary Application
- Direct and indirect air heating
- Applications
- Industrial Ovens And Furnaces, Glass Lehrs, Indirect‑Fired Air Heaters, RTO Incinerators, Afterburners, Galvanizing Kettles, Waterbath Vaporizers
Pressure Specifications
- Fuel Pressure Range
- Must meet datasheet specs; low pressure may cause unsafe operation
- Pressure Switch
- Detects low air pressure
Operating Limits, Durability & Lifecycle
- Altitude Adjustment
- Capacity reduced ~3% per 1000 ft above sea level
Standards & Certifications
- Safety Standards
- NFPA Compliant (e.g., dual gas shut-off valves)
Actuation, Valve & Motion Control Specifications
- Shut-Off Valves
- Automatic/manual, NFPA compliant
Safety, Protection & Reliability
- Safety Features
- Air pressure switch, flame monitoring, limit switches
- Hazard Warnings
- Hot surfaces, combustion risks, crystalline silica exposure
Control, Logic & Functional Behavior
- Ratio Regulator
- Maintains air/gas ratio via impulse line
Combustion Design & Characteristics
- Combustion Type
- Nozzle-mix, direct or indirect fired
- Combustor Tube
- Alloy (low temp), SiC or refractory block (high temp)
Performance, Flow & Capacity
- Turndown Ratio
- Wide turndown (high‑turndown option available)
Combustion Air, Blower & Emissions Specifications
- Blower Options
- Integrated or remote blower (SMJ series)
Product Design & Configuration
- Burner Family
- RatioAir®
- Burner Design
- Modular design with various configurations
Mechanical Design & Adjustment Characteristics
- Loading Line
- Plastic, Braided Stainless Steel, or Rigid Stainless Tube
Overview
- Burner Type
- Nozzle‑mix air‑heating burner
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas, Propane, Butane
| Parameter | Published value / configuration |
|---|---|
| Control Motor Specifications | ≤2 rpm, ≥25 in-lb torque, 90 deg stroke, reversible |
| Blower Motor Types | NEMA (60Hz), IEC (50Hz), TEFC or automotive duty |
| Control Motor | Kromschröder IC 20 actuator or bracket for customer motor |
| Combustion Air Requirements | Fresh (20.9% O₂), clean, ≤150 deg F (65 deg C) |
| Excess Air Capability | 10 to 15% at high fire; Higher at low fire |
| Air/Gas Ratio Control | Ratio regulator with impulse line |
| Ignition Transformer Specs | 6000 to 8000 VAC, ≥ 0.02 A, Full wave output |
| Flame Supervision | Flame rod (RA0025 to RA0200), UV scanner (all models) |
| Flame Monitoring | Individual or multiple burner control options |
| Ignition Type | Direct Spark Ignition (low fire or bypass start gas) |
| Flame Sensor | Flame rod or UV scanner |
| Outlet Tube Velocity | Standard, Medium (250 ft/s), High (500 ft/s) |
| Combustion Principle | Nozzle‑mix burner |
| Burner Configuration | Vertical Down, Vertical Up, Horizontal |
| Primary Application | Direct and indirect air heating |
| Applications | Industrial Ovens And Furnaces, Glass Lehrs, Indirect‑Fired Air Heaters, RTO Incinerators, Afterburners, Galvanizing Kettles, Waterbath Vaporizers |
| Fuel Pressure Range | Must meet datasheet specs; low pressure may cause unsafe operation |
| Pressure Switch | Detects low air pressure |
| Altitude Adjustment | Capacity reduced ~3% per 1000 ft above sea level |
| Safety Standards | NFPA Compliant (e.g., dual gas shut-off valves) |
| Shut-Off Valves | Automatic/manual, NFPA compliant |
| Safety Features | Air pressure switch, flame monitoring, limit switches |
| Hazard Warnings | Hot surfaces, combustion risks, crystalline silica exposure |
| Ratio Regulator | Maintains air/gas ratio via impulse line |
| Combustion Type | Nozzle-mix, direct or indirect fired |
| Combustor Tube | Alloy (low temp), SiC or refractory block (high temp) |
| Turndown Ratio | Wide turndown (high‑turndown option available) |
| Blower Options | Integrated or remote blower (SMJ series) |
| Burner Family | RatioAir® |
| Burner Design | Modular design with various configurations |
| Loading Line | Plastic, Braided Stainless Steel, or Rigid Stainless Tube |
| Burner Type | Nozzle‑mix air‑heating burner |
| Fuel Type | Natural Gas, Propane, Butane |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 10002787 | CMBSTR,ALLY,686MM LG,300MM OUTLT,SZ 7,AI | Request quotation |
| 10005394-3 | CMBSTR,ALLY,544MM LG,300MM OUTLT,SZ 7,AI | Request quotation |
| 10012506 | SHIM,BDY,SZ 7 | Request quotation |
| 10015028-1 | PLT,DIFFSR,AIR,33% OPEN AREA | Request quotation |
| 10015028-2 | PLT,DIFFSR,AIR,50% OPEN AREA | Request quotation |
| 10053451-1 | KIT,LIT,RA,RA0025,ENG | Request quotation |
| 10053451-10 | KIT,LIT,RA,RA1500,ENG | Request quotation |
| 10053451-11 | KIT,LIT,RA,RA2000,ENG | Request quotation |
| 10053451-2 | KIT,LIT,RA,RA0040,ENG | Request quotation |
| 10053451-3 | KIT,LIT,RA,RA0075,ENG | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
image · Manufacturer ownership retained; republication licence not independently confirmed
RatioAir Product Image 1 · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.