Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Burner Accessories

Blast Tips

Blast Tips produce retained flames without requiring a refractory tunnel under normal operating conditions.

Blast Tips produce retained flames without requiring a refractory tunnel under normal operating conditions. Individual tips are matched to fuel behavior; suitability for one gas does not establish suitability for another. Groups can heat broad surfaces or extend along a pipe, including kettle-bottom and core-oven arrangements.

Features & Benefits

Sizes
Ferrofix - 1/4 to 6 in pipe sizes|Sticktite - 1/2 to 6 in pipe sizes
Flame Supervision
Suitable flame sensing and automatic fuel shutoff required
Compatible Mixers
Injectors (low/high pressure), proportional mixers, Variset® mixers
Mixture Pressure
Rated at 6 in. wc (15 mbar)
Combustion Block
Not required; optional for refractory‑lined chambers
Capacity Range
Ferrofix - 6,090 to 5,700,000 BTU/hr (HHV) at 6 in. wc|Sticktite - 37,000 to 5,250,000 BTU/hr (HHV) at 6 in. wc
Nozzle Series
Ferrofix, Sticktite
Mixing Method
Used with air/gas mixing devices
Typical Uses
Boilers, kilns, ovens, air heaters, furnaces, immersion heating
Nozzle Type
Open‑type, flame‑retention design
Material
Cast Iron, Steel
Gas Type
Natural Gas (0.6 specific gravity reference)

Applications

  • Kettle-bottom heating
  • Core-oven heating

Specifications

Dimensions & Size Specifications

Sizes
Ferrofix - 1/4 to 6 in pipe sizes; Sticktite - 1/2 to 6 in pipe sizes

Ignition, Flame & Supervision Specifications

Flame Supervision
Suitable flame sensing and automatic fuel shutoff required

Applications & Compatibility

Compatible Mixers
Injectors (low/high pressure), proportional mixers, Variset® mixers
Typical Uses
Boilers, kilns, ovens, air heaters, furnaces, immersion heating

Pressure Specifications

Mixture Pressure
Rated at 6 in. wc (15 mbar)

Combustion Design & Characteristics

Combustion Block
Not required; optional for refractory‑lined chambers

Processing & Performance Metrics

Capacity Range
Ferrofix - 6,090 to 5,700,000 BTU/hr (HHV) at 6 in. wc; Sticktite - 37,000 to 5,250,000 BTU/hr (HHV) at 6 in. wc

Combustion, Fuel & Mixing Sub‑Systems

Nozzle Series
Ferrofix, Sticktite
Nozzle Type
Open‑type, flame‑retention design

Combustion, Mixing & Fuel Dynamics

Mixing Method
Used with air/gas mixing devices

Material Specifications

Material
Cast Iron, Steel

Fuel, Gas & Media Specifications

Gas Type
Natural Gas (0.6 specific gravity reference)
Blast Tips — manufacturer page values
ParameterPublished value / configuration
SizesFerrofix - 1/4 to 6 in pipe sizes; Sticktite - 1/2 to 6 in pipe sizes
Flame SupervisionSuitable flame sensing and automatic fuel shutoff required
Compatible MixersInjectors (low/high pressure), proportional mixers, Variset® mixers
Typical UsesBoilers, kilns, ovens, air heaters, furnaces, immersion heating
Mixture PressureRated at 6 in. wc (15 mbar)
Combustion BlockNot required; optional for refractory‑lined chambers
Capacity RangeFerrofix - 6,090 to 5,700,000 BTU/hr (HHV) at 6 in. wc; Sticktite - 37,000 to 5,250,000 BTU/hr (HHV) at 6 in. wc
Nozzle SeriesFerrofix, Sticktite
Nozzle TypeOpen‑type, flame‑retention design
Mixing MethodUsed with air/gas mixing devices
MaterialCast Iron, Steel
Gas TypeNatural Gas (0.6 specific gravity reference)

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

1 parts

Part NumberDescriptionEnquiry
18903-1NZL,STICKTITE,ST 103 14,0.75 IN.,NPT,STLRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/burner-accessories/blast-tips

Last source check: 2026-11-02

Open Burner Nozzle Product Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry