Ignition Components
Q624 Ignition Transformer
Q624 is an interrupted-ignition transformer for gas pilots, with a published 15,000 V peak output and spark gaps up to 1/4 inch.
Q624 is an interrupted-ignition transformer for gas pilots, with a published 15,000 V peak output and spark gaps up to 1/4 inch. It fits conventional transformer space while reducing weight. Correct use with the listed MiniPeeper UV sensors prevents the detector from treating the ignition spark as a flame.
Features & Benefits
- Ambient Temperature Range
- -40 to +125°F (-40 to +52°C)
- Maximum Lead Length
- 15 ft (4.6 m) High Voltage
- Primary VA Rating
- 66 VA at 120 VAC
- Power Dissipation
- ~12 watts per second
- Energy Discharge
- 200 millijoules per spark
- Ambient Humidity
- 95% RH
- Output Voltage
- 15,000 V peak (firing cycle), 22,000 V peak-to-peak (nonsinusoidal)
- Mounting Types
- Surface mount
- Discharge Time
- 0.3 milliseconds per spark
- Firing Rate
- 60 sparks per second
- Spark Gap
- Up to 1/4 in (6 mm)
- Frequency
- 50/60 Hz
- Temperature Range
- -40 to +125°F
- Approximate, Dimensions
- 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep)
- Weight lb. (kg)
- 3 lb (1.4 kg)
- Approvals, Underwriters Laboratories Inc.
- Component Recognized Approvals, CSA: Certified: File No. LR95329
- Operating Humidity Range (% RH)
- 95% RH
- Lower weight simplifies replacement in conventional transformer space.
Applications
- Interrupted gas-pilot ignition
Detailed capabilities
Ignition duty and flame-detector interaction
Q624 is limited to interrupted ignition, with its peak output intended for the stated gas-pilot gap. Correct installation with C7027/C7035/C7044 avoids falsely detecting the spark. The mounting envelope matches conventional transformers while reducing weight. Temperature, humidity and approval facts belong to the specified transformer; they do not authorize continuous ignition or a larger electrode spacing than the published limit.
Features and benefits
- Lower weight simplifies replacement in conventional transformer space.
Published application context
- Interrupted gas-pilot ignition
Technical facts in the product overview
- Temperature Range: -40 to +125°F
- Approximate, Dimensions: 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep)
- Weight lb. (kg): 3 lb (1.4 kg)
- Approvals, Underwriters Laboratories Inc.: Component Recognized Approvals, CSA: Certified: File No. LR95329
- Operating Humidity Range (% RH): 95% RH
Environmental Conditions
- Ambient Temperature Range
- -40 to +125°F (-40 to +52°C)
- Ambient Humidity
- 95% RH
Dimensions & Length Specifications
- Maximum Lead Length
- 15 ft (4.6 m) High Voltage
Electrical Specifications
- Primary VA Rating
- 66 VA at 120 VAC
- Power Dissipation
- ~12 watts per second
- Output Voltage
- 15,000 V peak (firing cycle), 22,000 V peak-to-peak (nonsinusoidal)
- Frequency
- 50/60 Hz
Actuation, Valve & Motion Control Specifications
- Energy Discharge
- 200 millijoules per spark
- Discharge Time
- 0.3 milliseconds per spark
Installation & Mounting Specifications
- Mounting Types
- Surface mount
Applications & Compatibility
- Applications
- Ignites gas pilots on commercial or industrial gas burners; not recommended for oil ignition
Ignition, Flame & Supervision Specifications
- Firing Rate
- 60 sparks per second
- Spark Gap
- Up to 1/4 in (6 mm)
Technical Specifications
- Temperature Range
- -40 to +125°F
- Approximate, Dimensions
- 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep)
- Weight lb. (kg)
- 3 lb (1.4 kg)
- Approvals, Underwriters Laboratories Inc.
- Component Recognized Approvals, CSA: Certified: File No. LR95329
- Operating Humidity Range (% RH)
- 95% RH
| Parameter | Published value / configuration |
|---|---|
| Ambient Temperature Range | -40 to +125°F (-40 to +52°C) |
| Ambient Humidity | 95% RH |
| Maximum Lead Length | 15 ft (4.6 m) High Voltage |
| Primary VA Rating | 66 VA at 120 VAC |
| Power Dissipation | ~12 watts per second |
| Output Voltage | 15,000 V peak (firing cycle), 22,000 V peak-to-peak (nonsinusoidal) |
| Frequency | 50/60 Hz |
| Energy Discharge | 200 millijoules per spark |
| Discharge Time | 0.3 milliseconds per spark |
| Mounting Types | Surface mount |
| Applications | Ignites gas pilots on commercial or industrial gas burners; not recommended for oil ignition |
| Firing Rate | 60 sparks per second |
| Spark Gap | Up to 1/4 in (6 mm) |
| Temperature Range | -40 to +125°F |
| Approximate, Dimensions | 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep) |
| Weight lb. (kg) | 3 lb (1.4 kg) |
| Approvals, Underwriters Laboratories Inc. | Component Recognized Approvals, CSA: Certified: File No. LR95329 |
| Operating Humidity Range (% RH) | 95% RH |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
6 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 32004766-001/U | Ignition cable assy | Request quotation |
| 32004766-002/U | 3.05M IGNITION CABLE FOR Q624 | Request quotation |
| 32004766-003/U | Ignition/flame rod cable priced per foot | Request quotation |
| Q624A1014/B | SPARK IGNITER | Request quotation |
| Q624A1014/U | IGNITION TRANSFORMER | Request quotation |
| S720A1040/U | IGNITION SPARK GENERATOR S720 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Q624 Product Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.