Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Ignition Components

Ignition transformers TZI, TGI

TZI/TGI supplies high voltage for gas- or oil-burner ignition, including single-electrode ignition and sensing arrangements.

TZI/TGI supplies high voltage for gas- or oil-burner ignition, including single-electrode ignition and sensing arrangements. Current specifications are separated from explicitly obsolete versions. The older TZI cabinet unit has IP00 protection, while TGI wall mounting has IP65; voltage and duty-cycle choices must follow the applicable generation.

Features & Benefits

Ambient Temperature Range
-20 to +60°C
Ignition Cable Length
Recommended < 1 m, max. 5 m
Electrode Distance
2 ± 0.5 mm
Enclosure Rating
TZI: IP 00, TGI: IP 65, NEMA 4.
Output Voltage
5 or 8 kV (model dependent)
Mains Voltage
120 VAC, 230 VAC, 50/60 Hz|TZI..Q, TGI..Q: 120 VAC, 50/60 Hz|TZI..W, TGI..W: 230 VAC, 50/60 Hz
Ignition voltage
5 to 8 kV
Duty cycle
19 to 33% or continuous operation

Applications

  • High-voltage gas- or oil-burner ignition

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +60°C
Enclosure Rating
TZI: IP 00, TGI: IP 65, NEMA 4.

Dimensions & Length Specifications

Ignition Cable Length
Recommended < 1 m, max. 5 m

Ignition, Flame & Supervision Specifications

Electrode Distance
2 ± 0.5 mm

Electrical Specifications

Output Voltage
5 or 8 kV (model dependent)
Mains Voltage
120 VAC, 230 VAC, 50/60 Hz; TZI..Q, TGI..Q: 120 VAC, 50/60 Hz; TZI..W, TGI..W: 230 VAC, 50/60 Hz

Applications & Compatibility

Applications
Gas burners, gas‑ignited oil burners; Used in furnaces, kilns, forging furnaces, and industrial heating systems.

Technical Specifications

Ignition voltage
5 to 8 kV
Duty cycle
19 to 33% or continuous operation
Ignition transformers TZI, TGI — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +60°C
Enclosure RatingTZI: IP 00, TGI: IP 65, NEMA 4.
Ignition Cable LengthRecommended < 1 m, max. 5 m
Electrode Distance2 ± 0.5 mm
Output Voltage5 or 8 kV (model dependent)
Mains Voltage120 VAC, 230 VAC, 50/60 Hz; TZI..Q, TGI..Q: 120 VAC, 50/60 Hz; TZI..W, TGI..W: 230 VAC, 50/60 Hz
ApplicationsGas burners, gas‑ignited oil burners; Used in furnaces, kilns, forging furnaces, and industrial heating systems.
Ignition voltage5 to 8 kV
Duty cycle19 to 33% or continuous operation

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
101040995TRNSFMR,IGN,TRK1 20PCUVD TR.K1 120V 50/6Request quotation
331193IGN.TRAF.TGI7/20R +VARIST.115VRequest quotation
607707IGN.TRAF.TGI 7/20 +VARIST.230VRequest quotation
HK405872PNL ASSY,OVC OIL VISCOSITY CTLRequest quotation
HK46402PNL ASSY,AUX W/RELAYSRequest quotation
HK56767R2382J BOX & MTR ASSY,ES25 100XRequest quotation
HK57530X024J BOX ASSY,W/24 TERMINALSRequest quotation
KS74923411TZI 5-15/100QZ (TRS515PCISOH1)Request quotation
KS74923412TZI 8-20/19QZ (TRE820PISOH1)Request quotation
KS74923414TZI 8-20/33QZ (TRS820PISOH1)Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/ignition-components/ignition-transformers-tzi-tgi